Data centers

The modular-core floor grille supplies the intake side of the racks. The hot aisle behind each row carries the exhaust air.

Two rows of server racks face a cold aisle with supply grilles in the raised floor. Teal lines follow supply air under the floor and up through the grilles to the rack intakes. Orange lines follow exhaust air to the overhead return. In the close-up, one of the four grille sections lifts out of its frame.

Trace the cooling air to the server intakes before ordering a floor grille. A raised floor can supply air between facing racks. On a slab floor with overhead supply, the cold aisle receives air from above.

Design decisions

Identify the intake side of each row
Mark rack intakes, exhausts, and containment doors on the plan. For underfloor supply, locate outlets in the cold aisle at the rack intakes. Show where hot air returns to the cooling unit so the supplier can distinguish supply grilles from return faces.
Compare airflow at the available pressure
Cable trays below the floor can restrict airflow. Ask for the airflow through each proposed grille at the pressure difference between the floor plenum and the aisle. Two grilles that fit the same opening can deliver different amounts of air.
Check the equipment move-in route
Mark any grille a loaded cart or rack will cross. Before approving that grille, ask the floor supplier for concentrated and rolling load test data for the proposed grille and its supports.

Product selection

  • Modular Core Floor Grilles, 3D renderingModular Core Floor Grilles

    Specify the removable-core option if individual sections need to lift out for service. Compare this grille for a cold-aisle opening once the floor supplier confirms the support detail and load capacity.

  • Removable Core Egg Crate Grille (Core with Protective Border), 3D renderingRemovable Core Egg Crate Grille (Core with Protective Border)

    The open grid provides a return face where the design ducts hot-aisle air back to the cooling unit. The border protects the edges of the core when staff remove it for cleaning.

Inquiry brief

Include these details when you request a quote.

  • Rack plan with intake and exhaust directions, containment boundaries, and quantities by supply or return opening.
  • Airflow per supply and return grille in cfm or L/s, and the available plenum-to-aisle pressure for floor outlets in inches of water or Pa.
  • Floor opening, panel thickness, and frame support dimensions in inches or mm. Show cable trays beneath the opening.
  • Required concentrated and rolling loads, the equipment travel route, and the floor system supplier's support drawing.